Sealed Lead Acid Batteries

6V 1.3AH Sealed Lead Acid Battery


LY11-030-15

  • The 'Online' range of sealed lead acid batteries are maintenance free, valve regulated and leak proof ideally suited to all 'standby applications'
  • There will be no loss in power output over the battery life.
  • Low self-discharge of about 2-3% per month compared with 20-30% for more common battery systems.
  • Quality construction with no compromise on materials to ensure a long service life.
  • Low internal resistance means a high discharge rate.
  • Wide operating temperature range operating between -15° C to +50 ° C when fully charged.

Specifications
Nominal Voltage 6V
Rated Cap 1.3AH
Approx Weight 0.30kg
Terminal Standard F3-TAB 187A
Optional
Operation Temperature
Charge 0°C (32°F) - 40°C (104°F)
Discharge -20°C (-4°F) - 50°C (122°F)
Storage -20°C (-4°F) - 40°C (104°F)
Capacity 25° (77°F) 20 hour rate (0.065A) 1.3AH
10 hour rate (0.117A) 1.17AH
5 hour rate (0.208A) 1.04AH
1 hour rate (0.78A) 0.78AH
Capacity affected by temperature 40°C (104°F) 103%
25°C (77°F) 100%
0°C (32°F) 86%
-15°C (5°F) 65%
Self-Discharge at 25ºC (77ºF) (Before recharge) Capacity after 3 month 91%
Capacity after 6 month 82%
Capacity after 12 month 64%
Constant voltage charge Cycle Initial Charging Current ≥0.39A 7.2V - 7.5V at 25°C (77°F)
Standby 6.8V - 6.9V at 25°C (77°F)
Max discharge current for 5 secretary 19.5A
Dimensions(mm)
Specifications
Time (mm) 5 10 15 20 30 60 120 180 300 600
Final voltage
1.80VPC A 3.170 2.321 2.127 1.530 1.181 0.722 0.433 0.316 0.206 0.113
W 17.522 13.215 9.978 8.859 6.842 4.235 2.566 1.864 1.225 0.736
1.75VPC A 3.334 2.407 2.228 1.605 1.276 0.780 0.449 0.286 0.208 0.117
W 18.285 13.851 11.004 9.271 7.092 4.489 2.660 1.934 1.271 0.741
1.70VPC A 3.610 2.550 2.348 1.688 1.300 0.787 0.475 0.347 0.227 0.124
W 19.311 14.174 11.433 9.622 7.321 4.567 2.730 1.993 1.307 0.745
1.65VPC A 3.824 2.654 2.568 1.733 1.326 0.797 0.476 0.347 0.227 0.125
W 20.213 14.586 11.511 9.856 7.388 4.625 2.761 2.009 1.322 0.747
1.60VPC A 4.063 2.765 2.600 1.781 1.369 0.810 0.485 0.314 0.230 0.127
W 20.581 14.842 11.728 9.800 7.466 4.657 2.781 2.020 1.330 0.747
Discharge Characteristics

Note: Discharge shall be cut-off at 5.25V if discharge at <1CA and at 4.8V if at ≥1CA It is recommended to recharge battery by constant-voltage charge immediately after use

Applications
  • Lighting Equipment
  • Emergency Lighting
  • Toys & Consumer Electronics
  • Fire Alarm & Security Systems
  • Electric Equipment and Telemeter Equipment
  • Portable Power Tools, Measuring and Medical Equipment